Source PDF · page 1
1. System overview
The ecoMain / ecoSub multi-channel energy monitoring system is suitable for residential, small and medium-sized commercial and industrial energy monitoring.
Application scenarios
One system: up to 13 × 3P or 40 × 1P meters
- Split design: main unit plus expansion units.
- Cascadable sub-units, expandable up to 40 channels.
- Power and data transmission via a single Ethernet cable.
- Voltage sensing via the main unit, with no additional voltage wiring required.
Features
- Modular design with maximum flexibility: Each module offers 10 channels, allowing expansion from 10 to up to 40 channels. Modules can be installed in different areas of a distribution cabinet to optimise space, with expansion when needed to avoid high initial investment.
- Modular & scalable: The brochure describes modular hardware supporting dozens to hundreds of circuits with flexible add-on devices and cost-adjustable investment.
- No complex wiring: Non-intrusive split-core current sensors measure current; voltage sampling is shared with the system power supply to simplify installation.
- Slim-form power sensor: Described as only 12 mm thick for compact cabinets. Adjustable phase and direction improve installation flexibility, with extendable cables to address cable-length needs.
- Wide platform compatibility: Native enecess cloud connectivity and open Modbus support for Home Assistant and other systems.
- Universal power compatibility: Supports single-phase, three-phase and split-phase circuits in residential and commercial applications.
Brochure wording: The single-system headline specifies up to 40 channels. The separate “dozens to hundreds of circuits” statement is not accompanied by a single-system configuration in this document. The brochure also uses both “12 mm” and a “12.4 mm” graphic label for the slim sensor; these are retained as source descriptions.
Source PDF · page 2
2. Modular components
Flexible module and channel expansion supports multi-circuit requirements in residential and commercial applications.
Main module (ecoMain)
- Integrated power supply and voltage measurement for easy wiring.
- Wi-Fi and Ethernet communication.
- Input voltage: 100–240 VAC, 50/60 Hz.
- Supports single-phase, split-phase and three-phase systems.
- 3 main circuits plus 10 branch circuits.
Sub module (ecoSub)
- Expands system monitoring to up to 40 channels.
- Power and data via a single Ethernet cable.
- Current sensors per channel, with shared voltage and configurable phase.
- Typical measurement accuracy: ±2%.
- 10 branch circuits per sub module.
Current sensor (ecoSensor)
- 30 A and 100 A models for branch and main circuits.
- Clip-on, non-intrusive installation with no wiring changes.
- Ultra-slim design for compact panels.
- High accuracy with long-term stability.
- Additional sensor specifications are available upon request.
Sensor extension cables
- Extend sensor connection distance for flexible installation.
- Anti-interference performance for stable signal transmission.
- Snap-lock connectors for fast and reliable installation.
Source PDF · page 3
3. Industrial design and highlights
No compromises on safety | Industrial-grade power supply
The brochure describes an independent power module combined with an industrial-grade design for reliability and long-term stability.
- PMU — Precision Measurement Unit, at the top of the exploded view.
- SCU — System Core Unit, in the middle.
- IPU — Independent Power Supply Unit, at the bottom.
Industrial highlights
Flexible monitoring channels
Modular design, expandable from 10 to 40 channels for flexible monitoring in residential and commercial environments.
One cable for all
A single cable delivers both power and communication, simplifying installation and enabling flexible system expansion.
Ultra-thin
Proprietary ultra-thin sensors reduce installation effort. The illustration labels sensor thickness as 12.4 mm and compares it with a 13.18 mm phone.
Flip-open design
Foldable clip-on design enables installation without interrupting the circuit.
External antenna
External antenna enables flexible installation and improved signal coverage.
Reliable wired connection
Reliable wired communication for stable and uninterrupted data transmission.
Plug design
Quick-connect design ensures reliable operation and eliminates complex wiring.
Extension cables
Extension cables can be added to reach remote measurement points for simplified installation. The source tile is labelled “Strethable Cables”.
Source PDF · page 4
4. Easy installation and configuration
The brochure provides the following installation and configuration overview.
-
Mount the monitor on DIN rails
Mount ecoMain on DIN rails in the distribution board and press until it clicks. Repeat for an optional ecoSub expansion unit if needed.
Step 1. -
Connect the sensors
Clamp the sensors onto the monitored branch cable and plug the other end into the monitor.
Step 2. -
Download the app and set up
Download the enecess app for Android or iOS from the official app store, install it, and follow the in-app guide to set it up.
Step 3. -
Start monitoring
Use your phone to monitor home energy consumption anytime, anywhere.
Step 4.
Three steps to complete channel configuration
-
Channel naming
A visual channel mapping view shows the relationship between monitored circuits and sensors, making channel identification and naming quick and intuitive.
-
Sensor direction
Adjust sensor direction directly in the software without reinstalling or repositioning the sensors.
-
Phase identification
Built-in automatic phase identification matches phases, reducing manual configuration and commissioning effort.
Source PDF · page 4
5. Advanced app features
Multi-site management
Centralize management of multiple sites and monitor system performance, device status and alarms from a single platform.
Visualized revenue tracking
Visualize energy generation, savings and financial returns to understand project performance and business value.
Automated report generation
Generate standardized operational reports automatically, making data collection and reporting faster and more efficient.
One-click data export
Export historical data and reports for further analysis, project documentation and long-term record management.
Source PDF · page 5
6. Multisystem
The brochure illustrates multiple ecoMain systems linked to one enecess app account, including:
- Single account management.
- ecoMain consolidation.
- Multi-floor deployment.
- Multi-panel installation.
Source PDF · page 5
7. Multi-mode data access
enecess offers cloud services, mobile apps, Home Assistant integration and open Modbus support. Both cloud and local data access are supported, enabling users to collect and view data independently of cloud services.
Source PDF · page 6
8. Product interface
Master interface (ecoMain)
- Main sensors interface: #1–#3.
- Branch sensors interface: #1–#10.
- LAN interface.
- Wi-Fi antenna.
- Power indicator.
- Communication indicator.
- Work status indicator.
- Reset button.
- Wi-Fi connection button.
- DIN rail clip.
- Power cable interface.
- ecoBus interface to the next unit.
Slave interface (ecoSub)
- Branch sensors interface: #1–#10.
- Power indicator.
- Communication indicator.
- Work status indicator.
- Reset button.
- ecoBus address button: #1–#3.
- DIN rail clip.
- ecoBus interface to the preceding unit.
- ecoBus interface to the next unit.
Source PDF · page 7
9. Specifications
The following tables transcribe the brochure specifications. Units and spacing are normalised for web reading; numerical values and qualifiers are retained.
ecoMain
| Item | Specification | Description |
|---|---|---|
| General information | Dimensions (H × W × D) | 73 mm × 78 mm × 66 mm |
| General information | Net weight | 223 g |
| Measurement parameters | Supported electrical systems | Single-phase 2-wire, split-phase 3-wire, three-phase 4-wire Wye (Y) |
| Measurement parameters | Maximum voltage measurement | 260 VAC Line-to-Neutral (L-N) |
| Measurement parameters | Voltage measurement channels | 3 phases (L1, L2, L3) |
| Measurement parameters | Current measurement channels | 3 × 100 A (main circuits), 10 × 30 A (branch circuits) |
| Measurement parameters | Energy measurement accuracy | ±2% (Typical) |
| Power supply | Operating power supply | 100–240 VAC Line-to-Neutral, 50/60 Hz |
| Power supply | Power consumption | <3 W |
| Communication parameters | Wi-Fi | 2.4 GHz IEEE 802.11 b/g/n, Max EIRP 20 dBm |
| Communication parameters | Bluetooth | Bluetooth v4.2, Max EIRP 10 dBm |
| Communication parameters | Ethernet | 10/100Base-T |
| Environmental parameters | Operating temperature | 0–40°C |
| Environmental parameters | Operating humidity | 20–80% |
| Environmental parameters | Storage temperature | -20–55°C |
ecoSub
| Item | Specification | Description |
|---|---|---|
| General information | Dimensions (H × W × D) | 36 mm × 78 mm × 66 mm |
| General information | Net weight | 85 g |
| Grid-tied power generation acquisition | Number of acquisition channels | 3 channels for 3-phase or 10 channels for single-phase power generation grid-tied point acquisition |
| Grid-tied power generation acquisition | Current acquisition channels | 10 branch grid-tied point currents |
| Data communication | ecoBus | Custom bus, supporting communication and power supply with the upper-level ecoMain and cascaded ecoSub units |
| Power supply | Power supply | Powered by ecoMain |
| Power supply | Power consumption | 1 W |
| Environment | Operating temperature | -20°C to +60°C |
| Environment | Storage temperature | 20°C to +80°C (as printed in source) |
ecoSensor (30 A)
| Item | Specification | Description |
|---|---|---|
| General information | Dimensions (H × W × D) | 73 × 78 × 66 mm (as printed in source) |
| General information | Net weight | 38 g |
| Measurement parameters | Maximum current | 30 A |
| Measurement parameters | Maximum voltage | 250 V (Primary) / 333 mV (Secondary) |
| Measurement parameters | Cable length | 0.4 m |
| Measurement parameters | Maximum measurable cable diameter | 8 mm |
| Measurement parameters | Measurement accuracy | ±1% (Typical) |
ecoSensor (100 A)
| Item | Specification | Description |
|---|---|---|
| General information | Dimensions (H × W × D) | 34 × 30.7 × 49 mm |
| General information | Net weight | 101 g |
| Measurement parameters | Maximum current | 100 A |
| Measurement parameters | Maximum voltage | 250 V (Primary) / 333 mV (Secondary) |
| Measurement parameters | Cable length | 0.8 m |
| Measurement parameters | Maximum measurable cable diameter | 16 mm |
| Measurement parameters | Measurement accuracy | ±1% (Typical) |
Source specification notes: The PDF prints ecoSub storage temperature as “20°C ~ +80°C” and ecoSensor (30 A) dimensions as “73×78×66mm”. These values are reproduced as printed and should be confirmed with enecess before they are used for product selection or installation.
Source PDF · page 7
10. Publisher contact
Website:
www.enecess.com
Email:
support@enecess.com